Part Number: THQB32100 | Manufacturer: General Electric Company | NSN: 5925-01-035-6739 (5925010356739) | |
Item Name: circuit breaker | CAGE Code: 93351 |
Please utilize the RFQ form below to submit an online quote request for NSN part number THQB32100 of Circuit Breaker by manufacturer General Electric Company having CAGE Code 93351 with NSN number 5925-01-035-6739. Please also fill the requested quantity and need by date form fields for your required part THQB32100. This information will help us prioritize your request effectively.
“*” Symbols for mandatory fields
Aerospace Orbit is owned and operated by ASAP Semiconductor – an AS9120B, ISO 9001:2015, and FAA AC 00-56B distributor of General Electric Company NSN parts. We stock difficult-to-find parts from more than 75,000 manufacturers. Request a quote for part number THQB32100 and an account manager will contact you shortly.
Our industry relationships allow us to assure competitive prices on all obsolete parts, and shorten the supply chain to deliver as soon as possible. You will receive a response within 15 minutes from a sales representative at Aerospace Orbit. Additionally, you can call us at +1-714-705-4780 or submit a Bill of Materials (BOM) to sales@aerospaceorbit.com to expedite the purchase process.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-035-6739 Item Description: Circuit Breaker | 5925 | 010356739 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Thqb32100 | 5 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 3.250 INCHES MINIMUM AND 3.310 INCHES MAXIMUM |
ADAT | BODY WIDTH | 2.970 INCHES MINIMUM AND 3.030 INCHES MAXIMUM |
ADAU | BODY HEIGHT | 2.330 INCHES MINIMUM AND 2.390 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.984 INCHES MINIMUM AND 1.000 INCHES MAXIMUM |
AJEC | BOSS HEIGHT | 0.150 INCHES MINIMUM AND 0.210 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 3 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 3 TERMINAL |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.800 MINIMUM AT 200 PCT ALL LOCATIONS AND 120.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CRTL | CRITICALITY CODE JUSTIFICATION | FEAT |
FEAT | SPECIAL FEATURES | MISSILE,MX PEACEKEEPER WEAPONS SYSTEM |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 3 COMPRESSION AND 3 TAB, SOLDER LUG |